No Cooling at All Lights On Cold Compressor Compressor Runs on Test
If the compressor runs fine on the test cord, check the
supply circuit to the compressor for 110 VAC. If power is present,
the existing compressor starting circuit is faulty. Either
permanently install a hard start kit (the fastest solution) or order
and install a limit and starting relay (and a capacitor if one is in
the circuit). If no power is found, trace the circuit as described
under Lights Off (or, for more information,
see Manual 5: Electricity Made Simple /
Electrical Safety).